Brand Name : XG

Model Number : ZW32

Certification : ISO, type report

Place of Origin : XIAN, China

MOQ : 1 SET

Payment Terms : L/C, T/T, D/A, D/P, Western Union, MoneyGram

Supply Ability : 2000 SET

Delivery Time : 3-7 DAYS

Packaging Details : exporting package

Application : Outdoor

Rated Voltage : 11KV 24KV 22KV

Rated Current : 400A 630A, 1250A, 1600A, 2000A, 2500A, 3150A,

Rated Frequency : 50/60Hz

Poles No. : 3

Phase : 3

Medium : vacuum

Usage : pol mounted

Contact Now

1. Electric Operation Auto Recloser 33kv Outdoor Vacuum Circuit Breaker

ZW32-12 Series Outdoor High Voltage Vacuum Circuit Breaker is widely used in the power system of three-phase, which has AC 50Hz and 10~12Kv voltage level. The main function of the equipment is breaking and closing the loading current, and also it can protect electric consumption by tele-control and tele-monitor. Meanwhile, ZW32-12 can be used in both of Business biased and household biased.

2. Advantages:

2.1. It conforms to the national GB1984“High voltage alternating current circuit breaker”.

2.2 It conforms to professional standard JB3855“3.6~40.5 kV voltage vacuum circuit breaker outdoor exchange” and relevant IEC standard.

3. Condition:

Ambient temperature:-40°C~+40°C

Wind pressure:≤700Pa(equivalent to wind speed 34m/s)

Relative humidity:≤95%or≤90%

Altitude:≤2000m

Seismic intensity:≤8

*No fire, explosion, serious filthy, chemical corrosion and violent vibration of places.

4. Main technical parameters:

Item
Unit
Parameter
Rated Voltage
KV
12
Rated Insulation Level
1 Min power frequency witstand Voltage
Dry test
42
Wet Test
34
Lighting impulse withstand voltage(peak)
75
Rated Current
A
630
400
200
Rated short-circuit breaking current
KA
20
16
12.5
Rated opertaing sequence
O-0.3s-CO-180s-CO
Rated short-circuit breaking current time
Times
30
Rated short-circuit closed current(peak)
KA
50
Rated peak withstand current
50
Rated short-time withstand current
20
Rated short-circuit duration
s
4
opening time (magnetic releasing)
Max operating voltage
ms
23~45
Rated operating voltage
23~60
Min operating voltage
25~45
close time
ms
≤100
total break time
≤20
Mechanism life
Times
1000
rated input power of Storage energy motor
Times
40

5. Photo and drawing

Electric Operation ZW32 33kv Outdoor 33kv Auto Recloser

6. Factory

Electric Operation ZW32 33kv Outdoor 33kv Auto Recloser


Product Tags:

ZW32 33kv Auto Recloser

      

Outdoor 33kv Auto Recloser

      

3 Phase 33kv Auto Recloser

      
Best Electric Operation ZW32 33kv Outdoor 33kv Auto Recloser wholesale

Electric Operation ZW32 33kv Outdoor 33kv Auto Recloser Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Xi'an Xigao Electricenergy Group Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)